ASHRAE Standard 126-2016
من اهم الاعمال المسئول عنها مهندس الموقع في مجال HVAC هي الاختبارات علي دكتات الهواء ومن اهم الاكواد الي
بتتكلم عن النقطه دي SMACNA و ASHRAE
بتتكلم عن النقطه دي SMACNA و ASHRAE
INTRODUCTION TO STANDARD
First published in 2000, Standard 126 is a joint project of ASHRAE and the Sheet Metal and Air Conditioning Contractors’ National Association (SMACNA). It was created to provide
methods of testing to determine the strength and durability characteristics of HVAC ducts under various loading and environmental conditions. The intent of Standard 126 is to address all duct shapes and materials. To the project committee’s knowledge, no other publication addresses all of
the structural and durability tests as comprehensively as this standard, although individual tests are covered under other standards.
A standardized set of comprehensive tests is used to ensure that products meet minimum structural requirements, and to allow products to be compared to one another. Such tests should simulate structural stresses that the duct will experience in service and facilitate the application of safety
factors. These tests include pressurizing the ductwork, applying superimposed loads, dropping weighted implements for impact or puncture, applying tension to the duct, bending
flexible duct 180 degrees, subjecting the ductwork to temperature and humidity changes, and bursting or collapsing the duc twork under pressure. After an individual test or a series
of tests, leakage tests may be conducted to determine the effect of a structural or durability test on a specimen. During a test or series of tests, the ductwork is observed to determine
if there is degradation and permanent damage. Pass/fail criteria are determined by the sponsoring
agency, code officials, or other users of this standard. Recommended acceptance criteria are provided in Informative Annex C.
1. PURPOSE
This standard provides laboratory test procedures for the evaluation of HVAC air ducts.
2. SCOPE
2.1 This standard shall be used to determine the structural strength, dimensional stability, durability, and leakage characteristics of HVAC air ducts.
2.2 This standard does not address the following:
a. Fittings
b. Effects of aerosols, solid particulates, corrosive environments, or combustibility
c. Long-term effects of extended service
d. Seismic qualifications
e. Underground ducts
f. Plenums and equipment casings
DOWNLOAD
ليست هناك تعليقات:
إرسال تعليق